Product Model:BAC1010-MBus
Function Description:
BAC1010-MBus gateway can convert MBus to BACnet, with 1 Ethernet Port, 1 MBus Port. Connect 2 Wire MBus meter to Building control configuration software such as Johnson's Metasys, Honi's EBI or Niagara, Siemens' Insight or Desigo CC, Schneider's EBO, etc. Supported devices include MBus water meter, MBus energy meter, MBus heat meter, and Modbus devices.
This product is to replace the original XR1005-MBUS concentrator with a BACnet gateway. MBus concentrator and gateway functions are integrated into one device, there is no need to install two devices, which is convenient for customers to wire, saves installation space, and saves costs.
The gateway is configured using X2BACnet software. The "X" of X2BACnet represents various collection protocols, "2" is "To", ¡°BACnet" ultimately supports standard BACnet MSTP/IP.
Users can configure the project based on the on-site device list and forward it to a standard BACnet IP server. Upload to the hardware gateway, and BACnet clients can access the data of on-site devices through the gateway.
Note: The Modbus register of the gateway collection end starts with a decimal address of 1 (Base1) and a hexadecimal address of 0 (Base0).
Collection Model:
1¡¢MBus_WaterMeter 2¡¢MBus_EnergyMeter 3¡¢MBus_EnergyMeter_EN 4¡¢ ModbusTCPClient 5¡¢Simulator
Note:
1. 2-Wire MBus device can only be connected to the M+ and M- terminals of COM1 port, with a voltage of around 36V.
2. Connecting them in reverse can burn the gateway or meter, and any consequences caused by wiring issues are the responsibility of the customer Undertake.
3. When connecting a 2-wire MBus device, must use a 24V power supply. 4. Customers encounter non-standard MBus protocols that support paid custom development, which can generally be completed within 2 weeks.
Runtime environment:
OS£º Win7¡¢Win8¡¢Win10¡¢ Win11¡¢Win Server 2008¡¢Win Server 2016
The hardware gateway comes with a built-in web server that supports browsers such as Google Chrome, Microsoft Edge, Apple Safari, Firefox, Opera, and 360 Speed Mode.
Register Type&Num
The number of gateway registers is dynamically supported, and 256 points can be built for each register.
BACnet Register Type |
BACnet Register Number |
AI(Read Only) |
256 |
AO(R&W) |
256 |
AV(R&W) |
256 |
BI(Read Only) |
256 |
BO(R&W) |
256 |
BV(R&W) |
256 |
MSI(Read Only) |
256 |
MSO(R&W) |
256 |
MSV(R&W) |
256 |
Software Features£º |
- BTL Certificate and BACnet International corporate GoldMember; - Support MBus_WaterMeter(CJ188)¡¢MBus_EnergyMeter(CJ188)¡¢ MBus_EnergyMeter_EN¡¢ModbusTCPClient to BACnet IP; |
- Support total 11 object types:Al, AO, AV, BL, BO, BV,MSL,MSO,MSV,Schedule,Trend Log; |
- Support COV subscription function; |
- Support BBMD cross network segment access; |
- Support BACnet Alarm and Event; |
- Support JavaScript and Trigger to realize logic control; |
- Support Chinese tag names and descriptions; - X2BACnet software is easy configuration, with 256 points configurable within 15minutes. |
|
|
|
 |
|
|
Application Principle Diagram

|
|
|
Product Dimensions

If you need to develop a non-standard protocol , please contact us.
If it is best to express the device to our company, the development cycle is usually 2 weeks.
Tel: +86-021-58776098
E-mail: support@opcmaster.com sales@opcmaster.com
| |